Pinout and Wiring
These connectors are drawn from the point of view of looking into the socket from outside
the transmitter
Door Connector
A Door Positive
B RF525 Activator Positive
C Common Ground for Door and RF525
Lumberg Connector
1
2
3
4
5
6
Pin No RF512 Pinout RF515 Pinout RF516 Pinout
1 Thermistor External-2 External-2 Positive Pt100 Positive Voltage
Input
2 Thermistor External-1 External-1 Positive Pt100 Positive Current
Drive
3 Thermistor External-4
(Reserved for future use)
Reserved for future use
Do Not Connect
No Connection
4 Thermistor Common External Common Pt100 Negative Current
Drive
5 Thermistor External-3
(Reserved for future use)
Reserved for future use
Do Not Connect
Pt100 Negative Voltage
Input
6 No Connection No Connection No Connection
Power Connector
A Positive +5 VDC
B Negative Ground
Gateway Relay Outputs
The two relay outputs each accept a 2.5mm jack plug. These are individually controlled
SPST relay contacts. Comark provide 2 jack plugs for wiring external equipment to be
activated by the Gateway.
Ensure that any external equipment presents only a low voltage on the jack so
as to prevent any chance of personal injury due to electric shock should the jack
plug become disconnected.